Symmetrical component systems
Speed 0 = stopped. When stopped, the phasors can be set manually by moving the angle sliders.
The method of symmetrical components was introduced in 1918 by Charles Legeyt Fortescue. It is a mathematical tool for analysing unbalanced conditions (e.g. faults, short circuits, unbalanced loading) in an otherwise balanced three-phase electrical system.
The method decomposes any unbalanced set of three-phase quantities (voltages or currents) into three balanced three-phase systems:
This decomposition makes it possible to solve unbalanced conditions using balanced three-phase systems of voltages and currents, and single-phase models can be used for the calculation.
Symmetrical component systems are not only a mathematical interpretation of the three-phase system, they can also be identified in the electrical network. Their presence is used in power quality assessment (negative sequence) and in protection relays as a protection criterion (e.g. the appearance of a zero sequence component identifies a single-phase fault).
Basic symmetrical component systems:
-
Positive sequence component (index “1” or “+”)
- It is a three-phase system in which all phases have the same amplitude and a phase shift of 120°.
- The phase sequence is \(L1 \rightarrow L2 \rightarrow L3\).
- It creates a rotating magnetic field in the direction of the original system.
- It represents the normal balanced state of the network.
-
Negative sequence component (index “2” or “–”)
- It is also a balanced three-phase system with equal amplitudes and a phase shift of 120°.
- The phase sequence is \(L1 \rightarrow L3 \rightarrow L2\), i.e. opposite to the positive sequence.
- It creates a magnetic field rotating in the opposite direction to the original system.
- It appears during faults or unbalanced loading.
-
Zero sequence component (index “0”)
- It is a three-phase system in which all phases are identical (both amplitude and phase).
- The phase shift between the phases is zero (\(0°\)).
- It does not create a rotating magnetic field.
- It is alternating with the same frequency as the original system (not DC!).
- It appears during faults (e.g. a phase-to-earth fault) as well as with unbalanced loading.
Sequence parameters of electrical equipment
When analysing unbalanced conditions in an electrical network with connected equipment (transformers, generators, lines), equivalent circuits have to be set up and the electrical parameters of the equipment calculated in the sequence systems (positive, negative and zero). This approach makes the calculation of currents and voltages simpler, e.g. for unbalanced faults. For every three-phase device an equivalent circuit can be set up in the sequence systems and its electrical parameters (impedance, admittance) expressed in the sequence systems:
where
and the transformation matrix is
Calculation of the positive, negative and zero sequence impedance from the matrix of self and mutual impedances of a three-phase device:
where \(a = e^{j\,120°}\).
From the point of view of electrical parameters and equivalent circuits in the individual sequence systems, electrical equipment can be divided into three groups:
-
Static (non-rotating) equipment without magnetic coupling between phases
-
The electrical parameters and equivalent circuits are the same in all sequence systems, their values do not depend on the phase sequence of the applied voltage:
\[R_1 = R_2 = R_0, \quad X_1 = X_2 = X_0, \quad \bar{Z}_1 = \bar{Z}_2 = \bar{Z}_0\]
- This group includes e.g. series reactors (air-core reactors for limiting short-circuit currents) and capacitors.
-
The electrical parameters and equivalent circuits are the same in all sequence systems, their values do not depend on the phase sequence of the applied voltage:
-
Static (non-rotating) equipment with magnetic coupling between phases
-
The electrical parameters and equivalent circuits in the positive and negative sequence systems are the same, their values do not depend on the phase sequence of the applied voltage:
\[R_1 = R_2, \quad X_1 = X_2, \quad \bar{Z}_1 = \bar{Z}_2\]
- The electrical parameters and equivalent circuits in the zero sequence system depend on the design of the equipment and on the earthing of the winding neutral. This group includes transformers and lines.
-
The electrical parameters and equivalent circuits in the positive and negative sequence systems are the same, their values do not depend on the phase sequence of the applied voltage:
-
Rotating equipment with magnetic coupling between phases
-
The electrical parameters and equivalent circuits differ between the sequence systems. The values of the electrical parameters in the positive and negative sequence systems depend on the phase sequence of the applied voltage, while the equivalent circuits in the positive and negative sequence systems are the same:
\[R_1 \neq R_2 \neq R_0, \quad X_1 \neq X_2 \neq X_0, \quad \bar{Z}_1 \neq \bar{Z}_2 \neq \bar{Z}_0\]
- This group includes generators and motors.
-
The electrical parameters and equivalent circuits differ between the sequence systems. The values of the electrical parameters in the positive and negative sequence systems depend on the phase sequence of the applied voltage, while the equivalent circuits in the positive and negative sequence systems are the same:
In general, the equivalent circuits of electrical equipment in the positive and negative sequence systems are the same, while the equivalent circuits in the zero sequence system depend on the design of the equipment and on the earthing of the winding neutral.
Decomposition of a three-phase voltage system into symmetrical components and the inverse transformation.
Decomposition of three-phase voltages into symmetrical systems:
-
Positive sequence component for reference phase L1:
\[ \bar{U}_{1L1} = \bar{U}_1 = \frac{1}{3}\left( \bar{U}_{L1} + a\,\bar{U}_{L2} + a^2\bar{U}_{L3} \right) \]
-
Negative sequence component for reference phase L1:
\[ \bar{U}_{2L1} = \bar{U}_2 = \frac{1}{3}\left( \bar{U}_{L1} + a^2\bar{U}_{L2} + a\,\bar{U}_{L3} \right) \]
-
Zero sequence component for reference phase L1:
\[ \bar{U}_{0L1} = \bar{U}_0 = \frac{1}{3}\left( \bar{U}_{L1} + \bar{U}_{L2} + \bar{U}_{L3} \right) \]
Transformation from symmetrical components back to the original three-phase system:
Or:
Transformation matrix from components to phases:
Transformation matrix from phases to components:
where the operator \(a = e^{j\,120°} = -\tfrac{1}{2} + j\tfrac{\sqrt{3}}{2}\), \(\;a^2 = e^{j\,240°} = -\tfrac{1}{2} - j\tfrac{\sqrt{3}}{2}\).