Short-circuit current waveform in a three-phase fault
Moving a slider = immediate recalculation
Calculation program for the analytical solution of the short-circuit current in a three-phase fault
The program calculates the short-circuit current in the reference phase L1 for a balanced three-phase fault in a simple circuit, where an ideal infinite bus (\(S_k'' = \infty\), \(\overline{Z}_{TS} = 0\)) supplies a load through a line. A three-phase fault is a symmetrical fault, so the solution is needed only in the positive sequence system. The subscripts follow the Slovak notation, TS for the infinite bus, ust for the steady state before the fault and ks for the AC component of the short-circuit current.
State before the fault – steady state
The short-circuit current is also influenced by the operating state before the fault. The initial value of the DC component of the short-circuit current \(i_{DC}(0)\) depends on the instantaneous value of the pre-fault current at the instant of fault inception \(i_{\text{ust}}(0)\). The pre-fault current is determined by the impedance of the circuit before the fault.
Line impedance:
Line admittance:
Load impedance (constant impedance model):
The line is represented by a gamma section with the shunt branch on the load side. In this case the impedance of the circuit before the fault is given by the impedance and admittance of the line and the load impedance:
With the option “admittance neglected” (\(\overline{Y}_{v} = 0\)) the expression simplifies to \(\overline{Z}_{\text{ust}} = \overline{Z}_{v} + \overline{Z}_{\text{load}}\). At no load no current flows before the fault, with the admittance considered the capacitive charging current of the line flows.
Infinite bus voltage of the reference phase L1:
The sign of the angle \(\varphi_{\text{ust}}\) in the following expressions depends on the character of the pre-fault current. For an inductive load the current lags the voltage and the minus sign applies, for a capacitive load the current leads the voltage and the plus sign applies. Steady-state current before the fault:
Amplitude of the pre-fault current \(I_{ust\_m} = \sqrt{2}\,I_{\text{ust}}\). Waveform of the pre-fault current:
Instantaneous value of the pre-fault current (t = 0 s):
The results panel shows the signed value of the angle \(\varphi_{\text{ust}}\) (negative for a capacitive character), which covers both cases automatically.
State during the fault – transient
The short-circuit current follows from the solution of the differential equation of the fault circuit:
Impedance of the fault circuit:
In this case the short-circuit impedance is given by the line impedance and the fault location on the line:
In short-circuit calculations the shunt admittances of equipment are normally neglected, because their influence on the short-circuit impedance is minimal.
The displayed short-circuit current \(i_k(t)\) is the current supplied by the source. It flows through the busbar and the line section from the source to the fault location. The fault branch itself (the fault location) carries the sum of the currents from both sides, the source current plus the decaying current from the load side, which after the fault dies out freely with the time constant of the load branch (for the default parameters ≈ 1.2 ms, initial value \(i_{\text{ust}}(0)\)). From the continuity of currents on both sides it follows that the current in the fault branch starts from zero and within a few milliseconds equals the source current. The contribution of a passive load is therefore normally neglected in short-circuit calculations (the load is not a source of short-circuit current).
The short-circuit current is the sum of the periodic AC component (steady-state) and the aperiodic DC component (free response):
The current in a circuit with inductance cannot change abruptly, therefore \(i_{k}(0) = i_{\text{ust}}(0) = i_{\text{ks}}(0) + i_{DC}(0)\) must hold. At the instant of fault inception (t = 0 s) the instantaneous value of the short-circuit current \(i_k\) equals the instantaneous value of the pre-fault current \(i_{\text{ust}}\).
The initial value of the DC component of the short-circuit current \(i_{DC}(0)\) is given by the difference between the pre-fault current \(i_{\text{ust}}(0)\) and the AC component of the short-circuit current \(i_{\text{ks}}(0)\):
The DC component decays with a time constant given by the parameters of the fault circuit:
The AC component of the short-circuit current is given by the infinite bus (source) voltage and the short-circuit impedance:
\(\alpha\) defines the instant of fault inception, i.e. the angle of the voltage phasor of the reference phase L1 at the instant of fault inception: \( u_{TS\_L1}(t) = U_{TS\_L1\_m}\sin(\omega t + \alpha) \rightarrow u_{TS\_L1}(0) = U_{TS\_L1\_m}\sin(\alpha) \). \(U_{TS\_L1\_m}\) is the amplitude of the source phase voltage \(U_{TS\_L1\_m} = \frac{\sqrt{2}}{\sqrt{3}}U_{TS}\).
Total short-circuit current:
Maximum instantaneous value of the short-circuit current
The maximum instantaneous value of the short-circuit current occurs when the AC component reaches its first amplitude after fault inception, and it is given by the sum of the AC component amplitude and the value of the decaying DC component:
The time \(t_m\) at which the maximum instantaneous value of the short-circuit current is reached is given by the argument of the sine of the AC component of the short-circuit current:
The time \(t_m\) at which the maximum instantaneous value of the short-circuit current is reached is always less than 0.01 s, the maximum occurs within half a period after fault inception.
Analysis of the short-circuit current waveform
Influence of the ratio \(R_k/X_k\) on the short-circuit current
With regard to the electrical, thermal and mechanical effects of short-circuit currents, it is favourable if the DC (aperiodic) component decays as fast as possible, i.e. when its time constant \(T_{DC}\) is small.
A DC component that persists longer increases the instantaneous values of the short-circuit current and thus the dynamic stress on electrical equipment. It also increases the thermal effects of the fault, because it prolongs the time during which higher current values act. The amount of heat released is proportional to the integral \(\int i_{k}^{2}\,dt\), so slow decay of the DC component leads to higher thermal stress on network equipment.
In low-voltage (LV) and medium-voltage (MV) networks the circuit resistance is relatively large compared with its reactance, so the ratio \(R_k/X_k\) is higher. The DC component of the short-circuit current therefore decays fairly quickly and its influence on the fault current is less pronounced.
In contrast, in high-voltage (HV) and extra-high-voltage (EHV) networks the reactance is typically much larger than the resistance (\(X_k \gg R_k\)). The time constant therefore reaches higher values and the DC component decays slowly. As a result, the maximum instantaneous values of the short-circuit current are higher and equipment must be designed for greater electrodynamic and thermal stress.
It follows that the ratio \(R_k/X_k\) is one of the decisive parameters affecting the short-circuit current waveform, the magnitude of the peak current and the overall effects of the fault on the network and its equipment.
The individual cases can be shown in the interactive tool (α = 0°, P = Q = 0, admittance neglected, other parameters at default values):
| Case | Setting | Result |
|---|---|---|
| slowly decaying iDC | R₁ = 0.022 Ω/km (default) | TDC = 43.7 ms |
| fast decaying iDC | R₁ = 0.24 Ω/km | TDC = 4 ms |
| non-decaying iDC (theoretical case) | R₁ = 0 Ω/km | TDC = ∞ (Rk = 0) |
Influence of the pre-fault current character on the short-circuit current
The calculations are made for the most unfavourable instant of fault inception \(\alpha = 0°\) and the same RMS value of the pre-fault current \(I_{\text{ust}} \approx 2061\) A. Settings in the interactive tool (α = 0°, admittance neglected, other parameters at default values):
| Character of the pre-fault current | Setting | Consequence | ik(tm) |
|---|---|---|---|
| purely resistive | P ≈ 1290 MW, Q ≈ −335 MVAr | iust(0) = 0 A | 22 350.16 A |
| purely inductive | P = 0 MW, Q ≈ 1860 MVAr | iust(0) ≈ −Iust_m (negative amplitude of the pre-fault current) | 20 019.11 A |
| purely capacitive | P = 0 MW, Q ≈ −1093 MVAr | iust(0) ≈ +Iust_m (positive amplitude of the pre-fault current) | 24 681.20 A |
For the purely resistive character the negative Q compensates the line reactance so that the current is in phase with the source voltage (\(\varphi_{\text{ust}} = 0\)).
The character of the pre-fault current affects:
- the instantaneous values of the currents at the instant of fault inception \(i_{\text{ust}}(0)\), \(i_{\text{ks}}(0)\), \(i_{DC}(0)\),
- the maximum instantaneous value of the short-circuit current \(i_{k}(t_m)\), which is highest for a capacitive character and lowest for an inductive one.
Influence of the pre-fault current magnitude on the short-circuit current
The calculations are made for the most unfavourable instant of fault inception \(\alpha = 0°\) and an inductive pre-fault current (ratio P : Q = 3 : 1 as in the default state). Settings in the interactive tool (admittance neglected):
| RMS value Iust | Setting | ik(tm) |
|---|---|---|
| ≈ 2000 A | P ≈ 1448 MW, Q ≈ 483 MVAr | 21.14 kA |
| ≈ 500 A | P ≈ 325 MW, Q ≈ 108 MVAr | 22.05 kA |
| 0 A (no load) | P = 0, Q = 0, admittance neglected | 22.35 kA — the highest value |
According to EN 60909, short-circuit currents are calculated from the no-load state before the fault, i.e. the network load is not considered.
The magnitude of the pre-fault current affects:
- the instantaneous values of the currents at the instant of fault inception \(i_{\text{ust}}(0)\), \(i_{\text{ks}}(0)\), \(i_{DC}(0)\),
- the maximum instantaneous value of the short-circuit current \(i_{k}(t_m)\).
Influence of the instant of fault inception on the short-circuit current
The calculations are made for the no-load state, i.e. zero pre-fault current (P = Q = 0, admittance neglected, otherwise the capacitive charging current of the line flows). In the tool it is enough to change α, the exact values (−4.17°, 85.83°) are entered in the numeric field “α exact” (for the default parameters \(\varphi_k = 85.83°\)):
| α | ik(tm) | tm | Note |
|---|---|---|---|
| α = 0° | 22 350 A | 9.77 ms | iDC(0) = 12 401 A — the most unfavourable instant of fault inception |
| α = \(\varphi_k\) − 90° = −4.17° | 22 324 A | 10 ms (half period) | maximum positive DC component, iDC(0) = 12 434 A |
| α = \(\varphi_k\) = 85.83° | 12 434 A | 5 ms (quarter period) | iDC(0) = 0 — no DC component |
| α = +90° | 11 624 A | 4.77 ms | at the positive voltage amplitude, iDC(0) = −903 A |
| α = −90° | −11 624 A | 4.77 ms | at the negative voltage amplitude, iDC(0) = +903 A |
The input of α is limited to the interval −90° to 90°. For α > 90° (e.g. 180°) the maximum of the short-circuit current within 0.01 s does not occur in the reference phase L1, but it does occur in another phase of the system (the calculation of tm applies analogously to a negative iDC(0)). For a negative α the first amplitude of the AC component in L1 falls on the opposite half-wave to the DC component, so the maximum does not occur in phase L1 and the tool shows, instead of ik(tm) of phase L1, the phase in which the maximum occurs. With the “3 phases” switch in the ACTION panel the waveforms of all three phases can be displayed, showing that outside the most unfavourable instant for L1 (e.g. for α < 0°) a phase other than L1 has the largest DC component and the largest instantaneous current.
The instant of fault inception affects:
- the instantaneous values of the currents at the instant of fault inception \(i_{\text{ust}}(0)\), \(i_{\text{ks}}(0)\), \(i_{DC}(0)\),
- the time at which the maximum instantaneous value of the short-circuit current is reached \(t_m\),
- the maximum instantaneous value of the short-circuit current \(i_{k}(t_m)\),
- the most unfavourable instant of fault inception is \(\alpha = 0°\) (or 180°).
Calculation according to EN 60909
The calculation of short-circuit currents according to the standard assumes the following simplifications:
- all line capacitances, shunt admittances and non-rotating static loads are neglected, except the shunt elements in the zero sequence system,
- all sources of short-circuit current are replaced by their internal impedance,
- the only active voltage source is the equivalent voltage source at the fault location, with voltage \(\frac{c\,U_{n}}{\sqrt{3}}\),
- c is the voltage factor. For the calculation of maximum short-circuit currents the factor c for the individual voltage levels is c = 1.05 (for 400 kV), c = 1.1 (for 110 kV, 22 kV, 400 V).
Initial symmetrical short-circuit current:
The initial symmetrical short-circuit current is the RMS value of the AC component of the short-circuit current \(I_{\text{ks}}\).
Peak short-circuit current:
The peak short-circuit current \(i_p\) is the maximum possible instantaneous value of the short-circuit current \(i_k(t_m)\) for the worst instant of fault inception \(\alpha = 0°\). K is the peak factor, which depends on the ratio \(R_k/X_k\):
Breaking current: for a far-from-generator fault the symmetrical short-circuit breaking current equals the initial symmetrical short-circuit current \(I_{b} = I_{k}''\).
Thermal equivalent short-circuit current for the fault duration \(T_k\):
For far-from-generator faults n = 1.