Transient behaviour of a synchronous generator with excitation and turbine control and damping
The model is a browser version of the interactive notebook by Karel Noháč (University of West Bohemia, Pilsen). It is based on Example 4-4 from the textbook Přenos a rozvod elektrické energie, Příklady (pp. 77 to 85, in Czech), the original notebook is in Google Colab. The choice of the fault type and of some network parameters was added. The classical equal area criterion without control is shown on the page Steady-state and transient stability of a synchronous generator. Indices in the symbols are Slovak, por = fault, vyp = clearing, TS = infinite bus, vs = local load, vz = base, tlm = damping, alt = alternator.
CALCULATION RESULTS
NETWORK AND TRANSMISSION
T2 340 MVA, 12 %, 220/121 kV
X₁ = 0.4 Ω/km, X₀ = 3 X₁
local load 50 MW, cos φ = 0.85
GENERATOR
base values S_vz = 255 MVA, U_vz = 215 kV
FAULT
CONTROL AND DAMPING
Using the model
The generator feeds an infinite bus through the generator step-up transformer T1, two parallel lines and transformer T2. A local load is connected at the generator terminals. At time \(T_{por}\) a fault occurs at the sending end of one of the lines, at time \(T_{vyp}\) this line is tripped. Sliders and switches recompute the whole transient immediately. The upper left plot shows the power-angle characteristics of the three states and the trajectory of the operating point, the upper right plot the load angle and the angular speed deviation, the lower left plot the generator power, the turbine power and their difference, and the lower right plot the voltage phasors before the fault.
With excitation control switched on, the trajectory does not lie on the drawn characteristics, because the electrical power is multiplied by the per-unit field current \(i_B\). The dashed green curve is the post-fault characteristic multiplied by \(i_B\) at the end of the simulation, the operating point finally oscillates around it. The turbine power drops to the power of the local load, so the new steady-state angle settles close to zero.
With both excitation and turbine control switched on, the generator stays in synchronism during a double line-to-ground fault for any clearing time. With both controls switched off, the model approaches the classical solution with constant \(u'_e\) and constant turbine power, and for the same fault it loses synchronism if the fault lasts longer than about 0.34 s. For a three-phase fault this is 0.42 s with control and 0.23 s without it.
Steady state before the fault
All quantities are in per-unit values with the base power \(S_{vz} = 255\) MVA and the base voltage \(U_{vz} = 215\) kV. Reactances of the components
From the given power to the network \(p_{TS} + j q_{TS}\) and the network voltage \(u_{TS}\), the generator terminal voltage and its angle are
The local load is replaced by a constant impedance \(\bar{z}_{vs} = u_G^2/(p_{vs} - j q_{vs})\). The generator output also includes the reactive losses on the external reactance
The transient EMF and its angle with respect to the network voltage
Power-angle characteristics of the three states
Because the local load lies between the generator and the network, the generator power is expressed through the self admittance \(\bar{y}_{11}\) and the transfer admittance \(\bar{y}_{12}\) between the voltage \(\bar{u}'_e\) and the network
The angles \(\beta\) are small and express the effect of the active part of the local load. Without the local load \(\beta_{11} = \beta_{12} = 0\) and the characteristic would be a pure sine. Before the fault
During the fault, the unbalanced fault is represented in the positive sequence system by an impedance \(\bar{z}_f\) connected at the fault location between T1 and the lines. Negative and zero sequence impedances seen from the fault location
The negative sequence impedance of the local load is 0.35 times the positive sequence one. The zero sequence impedance of the local load is infinite and the generator does not appear in the zero sequence system, because T1 has a delta winding.
| fault | \(\bar{z}_f\) |
|---|---|
| three-phase fault | \(0\) |
| double line-to-ground fault | \(\bar{z}_2 \parallel \bar{z}_0\) |
| line-to-line fault | \(\bar{z}_2\) |
| single line-to-ground fault | \(\bar{z}_2 + \bar{z}_0\) |
The admittances \(\bar{y}_{11}^{(II)}\) and \(\bar{y}_{12}^{(II)}\) are computed by the unit current method in the original notebook, in this model by solving two nodal equations (generator terminal node and fault node) with the network short-circuited. The result is the same. For a three-phase fault \(\bar{y}_{12}^{(II)} = 0\) and the generator delivers nothing to the network during the fault. After the faulted line is tripped
and the admittances are obtained in the same way as before the fault.
Control and the swing equation
Excitation control is represented by field forcing. From fault inception the field current rises with the time constant \(T_F\) up to 2.5 times its initial value, and in this simplification the electrical power of the generator is multiplied by the per-unit field current
where \(k\) is state I, II or III depending on time. After fault inception, turbine control reduces the turbine power to the power of the local load
With control switched off \(i_B = 1\) or \(p_T = p_G\), respectively. The transient is described by two first-order differential equations
with the initial conditions \(\vartheta(0) = \vartheta_0\) and \(\Delta\omega(0) = 0\). The original notebook solves them with the SciPy function odeint. In the browser they are solved by the 4th order Runge-Kutta method with a step of 0.5 ms, and the instants \(T_{por}\) and \(T_{vyp}\) are always step boundaries. The difference from a solution with a tolerance of 10⁻¹² is below 10⁻⁹ rad.
Loss of synchronism is declared when the angle exceeds \(\vartheta = 180^\circ\). The computation stops at 540°, the further course is not worth plotting.