Electric field strength around a single-circuit three-phase line

Electric field strength around a single-circuit three-phase line

Conductors L1, L2, L3, the ground wires and the observation point P can be dragged with the mouse or a finger. Both axes have the same scale.
FIELD STRENGTH AT POINT P
POLARIZATION ELLIPSE AT POINT P
DISPLAY
Color scale E [kV/m]
min max
CONDUCTOR ARRANGEMENT
The triangle is equilateral with a side of 6 m.
CONDUCTORS, VOLTAGES, GROUND WIRES AND OBSERVER
Bundle, number of sub-conductors spacing a [m]

Brief description of the calculation

The model calculates the electric field strength around three phases and at most two ground wires. Each phase is a bundle of one to four conductors, each sub-conductor of the bundle has its own row in the matrix \(\mathbf{P}\) and its own charge. The conductors are long, straight and parallel, the ground is a perfectly conducting plane at zero potential. The phase conductors are 476-AL1/62-ST1A and the ground wires 183-AL1/43-ST1A, the same as in the line parameters model. The color map shows the RMS value of the field strength \(E\) in the line cross-section.

Conductor charges

\[ P_{ii} = \frac{1}{2\pi\varepsilon_0}\ln\frac{2h_i}{r_i}, \qquad P_{ij} = \frac{1}{2\pi\varepsilon_0}\ln\frac{D'_{ij}}{D_{ij}}, \qquad \bar{\mathbf{q}} = \mathbf{P}^{-1}\,\bar{\mathbf{U}} \]

\(\mathbf{P}\) is the matrix of Maxwell's potential coefficients, \(h_i\) the conductor height, \(r_i\) its radius, \(D_{ij}\) the distance between conductors and \(D'_{ij}\) the distance of conductor \(i\) from the image of conductor \(j\). The vector \(\bar{\mathbf{U}}\) contains the phase-to-ground voltages, i.e. the entered line-to-line voltage divided by \(\sqrt{3}\). The ground wires are grounded and have zero voltage, their charge follows from the solution of the system.

Field strength at point P

\[ \bar{E}_x = \sum_{k} \frac{\bar{q}_k}{2\pi\varepsilon_0} \left(\frac{x_P - x_k}{r_k^{2}} - \frac{x_P - x_k}{r_k'^{2}}\right), \qquad \bar{E}_y = \sum_{k} \frac{\bar{q}_k}{2\pi\varepsilon_0} \left(\frac{y_P - y_k}{r_k^{2}} - \frac{y_P + y_k}{r_k'^{2}}\right) \]

\(r_k\) is the distance of point P from conductor \(k\) and \(r_k'\) from its image below the ground. At the ground surface the field has only a vertical component. The voltage waveform of the conductor is \(u_k(t) = \sqrt{2}\,U_k \cos\left(2\pi f_k t + \varphi_k\right)\).

RMS value

At the same frequency the contributions of the conductors add as phasors. If the conductors have different frequencies, the field is calculated for each frequency separately, and conductors with another frequency have zero voltage at it. The RMS values then add in quadrature

\[ E_{x} = \sqrt{\sum_{f}\left|\bar{E}_{x,f}\right|^{2}}, \qquad E_{y} = \sqrt{\sum_{f}\left|\bar{E}_{y,f}\right|^{2}}, \qquad E = \sqrt{E_x^{2} + E_y^{2}} \]

Polarization ellipse

At a single frequency the tip of the vector \(\mathbf{E}(t)\) traces an ellipse. Its major and minor semi-axes, expressed as RMS values, are \(E_{\max}\) and \(E_{\min}\), and \(E = \sqrt{E_{\max}^{2} + E_{\min}^{2}}\). If the conductors have different frequencies, the curve is no longer an ellipse and it is drawn over the common period of all frequencies. The scale of the ellipse axes adapts to the field magnitude.

Using the model

  • The conductors, the ground wires and point P can be dragged in the figure. The figure window adapts to the positions of the conductors, so a small model with dimensions in centimetres can also be simulated. The dragging step changes with the scale and is shown next to the snapping option. The coordinates can also be entered directly in the table to three decimal places.
  • Values typed in the table take effect after pressing the Apply button or the Enter key. The checkbox after the frequency switches the conductor on and off, a switched-off conductor is left out of the calculation completely, it is not even treated as grounded.
  • For each phase conductor, the line-to-line voltage, the phase angle and the frequency are set. The default is a balanced 420 kV, 50 Hz system with a triple bundle with 0.4 m spacing. At most two ground wires can be added. The bundle considerably increases the charge of the conductors and thus also the field strength near the ground. In the figure it is drawn as a single circle.
  • The range of the color scale is set in kV/m, the default is 0 to 10 kV/m. Values outside the range take the color of its limit. With a logarithmic scale and a minimum of 0, the scale starts three decades below the maximum.
  • The waveform plot shows two periods of the lowest frequency set. The range of the vertical axis adapts to the largest instantaneous value of the field.