Unbalance of overhead power lines

An overhead power line A power line is equipment for the transmission and distribution of electrical energy. Power lines connect the nodes of the power system (power plants, substations) at one voltage level.

Basic types of power lines:
- cable lines – have solid insulation and are used mainly for distribution at the LV and MV levels,
- overhead lines – the insulation is air, they are used mainly for distribution and transmission at the HV and EHV levels.

Main parts of an overhead power line:
- conductors – usually ACSR (AlFe) stranded conductors,
- towers – the supporting structure that holds the conductors in the air, keeps them at a safe height above ground and at the correct distance from each other,
- insulators – hold the conductors mechanically on the tower and insulate them from the tower structure,
- earth wire (shield wire) – protects the line against lightning, it is fixed directly to the tower (without insulators),
- optical ground wire (OPGW) – a special type of conductor with a protective (lightning) and a communication function.
is an inherently unbalanced three-phase device, because its electrical parameters depend on the mutual distances between the conductors (phase conductors and earth wires) and on the distance of the conductors from the ground.

The unbalance of a line is assessed by calculating the steady states on the line and analysing the state quantities voltage, current and power. These are expressed in symmetrical component systems Symmetrical components were defined in 1918 by Charles Legeyt Fortescue.

- The method of symmetrical components is a mathematical tool used in power engineering to solve unbalanced conditions (most often short circuits) in a balanced three-phase system.
- The method decomposes an unbalanced state of a three-phase system into three balanced three-phase systems, so single-phase models can be used for the solution.
- Symmetrical component systems are not only a mathematical interpretation of the three-phase system, they can also be identified in the electrical network. Their presence is used in power quality assessment (negative sequence) and in protection relays as a protection criterion (e.g. the appearance of a zero sequence component identifies a single-phase fault).

The symmetrical component systems are
- positive sequence, marked with the indices "1", "+"
- negative sequence, marked with the indices "2", "-"
- zero sequence, marked with the index "0"
, namely positive, negative and zero sequence.

The steady-state calculations in this example are carried out in Matlab Simulink (version 2019b).

The simulation model consists of these main parts:

  • Line – a distributed-parameter block that models the line as a three-phase object.
  • Source – represents the substation that feeds the line and from which power flows through the line.
  • Load – represents the substation to which the power flows through the line.
  • Measurement blocks – used to monitor and evaluate the electrical quantities.

Input data

  • 400 kV line
  • tower types Portal and Mačka
  • phase conductor:
    • 450 AlFe 6, d=29.76 mm, RAC=0.0673 Ω km-1, x=0.8123
    • bundle conductor (3-conductor bundle), bundle spacing a=0.4 m
    • max. sag 4 m
  • earth wire:
    • 185 AlFe 6, d=20.39 mm, RAC=0.164 Ω km-1, x=0.826
    • max. sag 4 m
  • earth resistivity: ρ=100 Ωm

Conductor coordinates on the tower

 
Tower type X cor L1 [m] X cor L2 [m] X cor L3 [m] Y cor L1 [m] Y cor L2 [m] Y cor L3 [m] X cor ZL1 [m] X cor ZL2 [m] Y cor ZL1 [m] Y cor ZL2 [m] number of earth wires number of circuits
PORTAL, tension -12.0 0 12.0 18.8 18.8 18.8 -6.0 6.0 31.8 31.8 2 1
MAČKA, suspension -6.8 0 6.8 18.0 18.0 26.7 -3.5 3.5 32.3 32.3 2 1

Description of model elements

Source – modelled as an ideal voltage source (ideal infinite bus), because the aim of the simulations is to analyse the properties of the line.

Voltage level. The voltage is given by the voltage level of the line. The specific value lies within the permitted voltage range. The ideal voltage source has zero internal impedance.

Node type in the network model – swing

Line – modelled with distributed parameters, because this block allows the line to be modelled as an unbalanced three-phase device.

The line parameters are calculated in Matlab (calculated electrical parameters) from the line geometry (Portal / Mačka).

Unbalanced line, parameters are given by 3x3 matrices calculated from the conductor geometry on the tower. Balanced line, parameters are given in the sequence systems, positive and negative.

Load – modelled as a balanced, purely resistive load, because only the properties of the line are analysed.

Choice of a voltage-dependent or voltage-independent load model

Measurement – the phase voltages and currents at the beginning and end of the line are evaluated

Powergui is a special Simulink block for SimPowerSystems / Simscape Electrical, used to configure and analyse electrical systems in both the time and the frequency domain.