Magnetic flux density around a single-circuit three-phase line
Brief description of the calculation
The model calculates the magnetic flux density around three phases without ground wires. Each phase is a bundle of one to four long straight conductors and each sub-conductor of the bundle is calculated separately. The ground is non-magnetic and does not affect the field, currents induced in the ground are neglected. The color map shows the RMS value of the flux density \(B\) in the line cross-section.
Instantaneous value
The sum runs over all sub-conductors of all bundles. \(I_k\) is the RMS current of conductor \(k\), \(\varphi_k\) its initial phase and \(f_k\) its frequency. The conductor lies at the point \((x_k, y_k)\), the observer at the point \((x_P, y_P)\).
RMS value
At the same frequency the contributions of the conductors add as phasors. Components with different frequencies are mutually orthogonal, so their RMS values add in quadrature
\(\bar{B}_{x,f}\) and \(\bar{B}_{y,f}\) are the phasors of the flux density components from all conductors with frequency \(f\). The resulting value \(B\) corresponds to the reading of a three-axis field meter.
Polarization ellipse
At a single frequency the tip of the vector \(\mathbf{B}(t)\) traces an ellipse. Its major and minor semi-axes, expressed as RMS values, are \(B_{\max}\) and \(B_{\min}\), and \(B = \sqrt{B_{\max}^{2} + B_{\min}^{2}}\). For \(B_{\min} = 0\) the field is linearly polarized, for \(B_{\max} = B_{\min}\) circularly. If the conductors have different frequencies, the curve is no longer an ellipse and it is drawn over the common period of all frequencies. The scale of the ellipse axes adapts to the field magnitude.
Using the model
- The conductors and point P can be dragged in the figure. The figure window adapts to the positions of the conductors, so a small model with dimensions in centimetres can also be simulated. The dragging step changes with the scale and is shown next to the snapping option. The coordinates can also be entered directly in the table to three decimal places.
- Values typed in the table take effect after pressing the Apply button or the Enter key. The checkbox after the frequency switches the conductor on and off, a switched-off conductor is not considered in the calculation.
- For each phase, the current of one sub-conductor of the bundle, the phase angle and the frequency are set. The default is a triple bundle with 0.4 m spacing and 800 A per sub-conductor, i.e. 2400 A per phase, 50 Hz. In the figure the bundle is drawn as a single circle.
- The range of the color scale is set in µT, the default is 0 to 50 µT. Values outside the range take the color of its limit. With a logarithmic scale and a minimum of 0, the scale starts three decades below the maximum.
- The waveform plot shows two periods of the lowest frequency set. The range of the vertical axis does not change with the phase, it is given by the sum of the amplitudes of the contributions of all conductors.