Overhead line parameters – impedance and admittance matrices
Brief description of the calculation
The model calculates the series impedance matrix \(\mathbf{Z}\) and the shunt admittance matrix \(\mathbf{Y}\) of an overhead line with one conductor per phase. The phase conductors are 476-AL1/62-ST1A, the ground wires 183-AL1/43-ST1A, the data come from the ELPAM conductor database and the resistances apply at 20 °C. The frequency is 50 Hz. Leakage is neglected, so \(\mathbf{Y} = j\mathbf{B} = j\omega\mathbf{C}\).
Impedance matrix
\(D_{ij}\) is the distance between conductors \(i\) and \(j\), \(D'_{ij}\) the distance of conductor \(i\) from the image of conductor \(j\), \(h_i\) the conductor height and \(\mathrm{GMR}_i\) the geometric mean radius of the conductor. The term \(\Delta Z_{ij} = \frac{\omega\mu_0}{\pi}\left(P_{ij} + jQ_{ij}\right)\) is Carson's correction for the current return through earth with resistivity \(\rho\). \(P_{ij}\) and \(Q_{ij}\) are calculated with Carson's series in the form given in the EMTP Theory Book for the parameter
For \(a > 18\) the asymptotic form is used, so the calculation is valid also for conductors at a height of 100 km.
Admittance matrix
\(\mathbf{P}\) is the matrix of Maxwell's potential coefficients with conductor images and \(r_i\) is the conductor radius. The off-diagonal elements of \(\mathbf{C}\) are negative.
Kron reduction of ground wires
The ground wires are grounded at every tower and their voltage to earth is zero. Their influence is transferred to the phase conductors by eliminating the rows and columns of the ground wires from the matrices (index f denotes phase conductors, z ground wires)
For capacitances the matrix \(\mathbf{P}\) is reduced first and only then inverted. The result is the same as the phase-conductor block of the inverse of the full matrix \(\mathbf{P}\), because \(\mathbf{C} = \mathbf{P}^{-1}\) already accounts for the ground wires at zero potential. For capacitances the reduction therefore only removes the rows and columns GW1 and GW2, the phase-conductor elements do not change. The influence of the ground wires on the capacitances is seen when a wire is added or removed. For impedances it is different. The phase-conductor block of the full matrix \(\mathbf{Z}\) corresponds to ground wires carrying no current, and the reduction changes it.
Sequence matrices
Index 0 denotes the zero, 1 the positive and 2 the negative sequence component. The sequence matrices are calculated from the 3 × 3 matrix, with ground wires always from the reduced one. On a perfectly transposed line the off-diagonal elements of the sequence matrices are zero. The equality \(Z_{11} = Z_{22}\) always holds.
Unbalance factors
The factor \(k_{Z2}\) tells how large a negative sequence voltage arises on the line for a purely positive sequence current, relative to the positive sequence voltage drop. The factor \(k_{Z0}\) gives the same for the zero sequence. The factors \(k_{Y2}\) and \(k_{Y0}\) express the negative and zero sequence charging currents for a purely positive sequence voltage. The row of an element is the component that arises, the column the component that causes it. On an untransposed line with conductors side by side the factors reach several percent, transposition reduces them almost to zero.
Per-unit values and matrix colouring
In per-unit values the phase matrices are referred to the element \(Z_{L1L1}\) or \(Y_{L1L1}\), the sequence matrices to the positive sequence elements \(Z_{11}\) and \(Y_{11}\). In the phase matrix each element is compared with the transposed line, i.e. with the mean of the diagonal or off-diagonal elements. The deviation referred to the mean diagonal element sets the intensity of the red colour, full red corresponds to 10 % or more. In the sequence matrix the off-diagonal elements are coloured by the ratio \(|X_{ij}|/|X_{11}|\). The matrix frame is coloured by the largest deviation.
Influence of conductor height
As the height increases, the self and mutual elements of the phase matrix \(\mathbf{Z}\) grow by the same amount, so the positive sequence impedance \(Z_{1}\) does not change and the positive sequence capacitance \(C_{1}\) changes only slightly. Positive sequence currents return through the other phases and do not need the earth. The zero sequence returns through the earth, so \(Z_{0}\) increases and \(C_{0}\) decreases with the logarithm of the height. At a height of 100 km the line behaves almost as in air without earth, but the zero sequence values remain finite.
Using the model
- The phase conductors L1, L2, L3 and the ground wires GW1, GW2 can be moved in the cross-section. With snapping on, the position is rounded to a 1 × 1 m grid, otherwise to 0.1 m.
- Coordinates can also be entered directly in the table. At most two ground wires can be added.
- The height slider on a logarithmic scale moves the whole arrangement from 1 m to 100 km.
- The switches in the DISPLAY section select the matrix form, the units, susceptance or capacitance and the Kron reduction of ground wires.
- Results are rounded to three decimal places. Hovering over a matrix element shows its name and deviation.