Single- and double-circuit overhead line – Z and Y matrices, per-phase π-section and losses
Brief description of the calculation
The model calculates the series impedance matrix \(\mathbf{Z}\) and the shunt admittance matrix \(\mathbf{Y}\) of an overhead line with one or two circuits. From the matrices it builds a per-phase π-section with a constant impedance load and determines the losses per phase, per circuit and in total. The phase conductor is a triple bundle or a single conductor 476-AL1/62-ST1A, the ground wires are 183-AL1/43-ST1A. The data come from the ELPAM conductor database and the resistances apply at 20 °C. The frequency is 50 Hz. Leakage is neglected, so \(\mathbf{Y} = j\mathbf{B} = j\omega\mathbf{C}\).
Triple bundle
The triple bundle consists of three sub-conductors at the vertices of an equilateral triangle with the side \(a = 0.4\) m. In the calculation it is replaced by one conductor at the bundle centre with an equivalent radius, an equivalent geometric mean radius and one third of the resistance
The phase coordinates apply to the bundle centre. The larger equivalent radius reduces the reactance and increases the line capacitance, the Joule losses at the same current drop to one third. The power transferred between the phases through the mutual inductances does not change at the same current and through the mutual capacitances it increases. With a triple bundle the power difference of one phase is therefore negative more often than with a single conductor. Compared with a calculation with three separate sub-conductors per phase the total losses differ by about 0.1 %.
Two circuits
With two circuits only the right circuit is set. The left circuit is its mirror image about the vertical tower axis, with the basic phase order the conductor L1′ has the coordinates \((-x,\, y)\) of the conductor L1. The ground wires are mirrored too, a wire on the tower axis (\(x = 0\)) stays single. The phase order switch of the left circuit determines which phase lies at the mirror positions of the conductors L1, L2, L3. In a rotation the phases shift cyclically, in a swap two phases are exchanged. The conductor positions stay the same, only the assignment of phases to conductors changes, and with it the coupling between the circuits. The matrices are 6 × 6 in the order L1, L2, L3, L1′, L2′, L3′. The diagonal 3 × 3 blocks are the self matrices of the circuits, the off-diagonal blocks describe the coupling between the circuits.
Impedance matrix
\(D_{ij}\) is the distance between the conductors \(i\) and \(j\), \(D'_{ij}\) the distance of the conductor \(i\) from the image of the conductor \(j\) in the earth, \(h_i\) the conductor height and \(\mathrm{GMR}_i\) the geometric mean radius of the conductor. The term \(\Delta Z_{ij} = \frac{\omega\mu_0}{\pi}\left(P_{ij} + jQ_{ij}\right)\) is Carson's correction for the current return through earth with resistivity \(\rho\). \(P_{ij}\) and \(Q_{ij}\) are calculated by Carson's series in the form given in the EMTP Theory Book for the parameter \(a = D'_{ij}\sqrt{\omega\mu_0/\rho}\). For \(a > 18\) the asymptotic form is used, so the calculation holds also for conductors at a height of 100 km.
Admittance matrix
\(\mathbf{P}\) is the matrix of Maxwell's potential coefficients with the images of the conductors and \(r_i\) is the conductor radius. The off-diagonal elements of the matrix \(\mathbf{C}\) are negative.
Kron reduction of the ground wires
The ground wires are earthed at every tower and their voltage to earth is zero. Their effect is transferred to the phase conductors by eliminating the rows and columns of the ground wires from the matrices (index f denotes the phase conductors, z the ground wires, from the Slovak zemné laná)
For the capacitances the reduction only removes the rows and columns of the ground wires, because \(\mathbf{C} = \mathbf{P}^{-1}\) already assumes the ground wires at zero potential. For the impedances the reduction changes the phase block. The block of the phase conductors in the full matrix \(\mathbf{Z}\) corresponds to ground wires carrying no current. After the reduction it includes the currents induced in the ground wires and with them their losses.
Sequence matrices
Index 0 denotes the zero, 1 the positive and 2 the negative sequence component. The sequence matrices are calculated from the matrices after the Kron reduction. With two circuits each 3 × 3 block is transformed separately. The element 00′ is the mutual zero sequence impedance of the circuits \(Z_{0m}\), the element 11′ the mutual positive sequence impedance \(Z_{1m}\). The zero sequence one does not depend on the phase order of the left circuit, the positive sequence one does. On a perfectly transposed line the off-diagonal elements of the blocks are zero and only the element 00′ remains of the coupling between the circuits.
Source and load
At the sending end of the line (index S) each circuit is fed by an ideal balanced source with the line-to-line voltage \(U_S\). The source phasors of the left circuit can be shifted against the right one by the angle \(\delta\) from −30° to 30°. At \(\delta = 0\) the same phases of both circuits have the same voltage, as on a common busbar. At the receiving end (index R) each circuit has its own load, so the circuits can be loaded differently. The load is a constant impedance in star connection with an earthed star point. It draws the specified power \(P + jQ\) at the voltage \(U_S\), the admittance of one phase is
The actual power drawn by a phase depends on the voltage at the receiving end, \(P_{R,k} = \frac{1}{3}P\,(U_{R,k}/U_f)^{2}\) with the phase voltage of the source \(U_f = U_S/\sqrt{3}\). Positive \(Q\) is an inductive load. At \(P = 0\) and \(Q = 0\) the circuit is open at the receiving end.
Per-phase π-section
The line of length \(l\) is replaced by a π-section with the series branch \(\mathbf{Z}\,l\) and with half of the shunt admittance \(\mathbf{Y}\,l/2\) at each end. The quantities are matrices and vectors of phasors of all phase conductors, three with one circuit, six with two. The couplings between the phases and between the circuits are preserved. The voltages at the receiving end follow from the nodal equations
\(\mathbf{Y}_{z}\) is the diagonal matrix of the load admittances. The currents of the series branch, the sending end and the receiving end are
The powers of the conductor \(k\) at both ends and their difference are
The voltages in the tables are phase-to-earth voltages. The replacement by a single π-section is accurate enough up to about 250 km.
Losses
The total losses \(\Delta P = \sum_k \Delta P_k\) over all phase conductors split into the Joule losses in the phase conductors, the Joule losses in the ground wires and the losses in the earth
\(I_i\) are the currents of the phase conductors in the series branch and \(I_z\) the currents induced in the ground wires. The losses in the earth are the remainder up to the total losses. They are caused by the currents induced in the earth, described by the real parts of Carson's corrections. The resistance of the phase conductors does not depend on the arrangement. The arrangement therefore changes the total losses only through the ground wires and the earth, that is by how well the effects of the currents of the individual phases cancel in them. At the same load the ratio of the total losses to the load differs between the preset arrangements without ground wires by about a tenth of a percent of its value. Ground wires increase it by 0.5 to 4 % with a triple bundle and by 0.2 to 1.3 % with a single conductor per phase. The split of \(\Delta P_k\) between the phases changes considerably, though.
Losses per circuit
With two circuits the power difference is also summed for each circuit separately. This difference does not equal the Joule losses in the conductors of the circuit. It also contains the active power that the circuits exchange through the mutual inductances and capacitances. With different loading one circuit therefore shows a larger power difference than the Joule losses in its conductors, and the other a smaller one. With the preset arrangements, the mirror phase order and a load of 500 and 200 MW it is at most 0.05 MW, considerably more is transferred between the phases. A rotation of the phases of the left circuit or a shift of its source angle increases this transfer, the power difference of one circuit then comes out even negative. The sum of both circuits is the actual line loss. The Joule losses in the ground wires and the losses in the earth cannot be assigned to one circuit, they belong to both.
Power transfer between phases
Each off-diagonal element of the matrices \(\mathbf{Z}\) and \(\mathbf{B}\) couples exactly two conductors, so it can be determined how much active power each pair exchanges. The power that the conductor \(i\) delivers to the conductor \(j\) through the mutual inductance and the mutual capacitance is
\(\bar{I}_i\) are the currents of the series branch. The power difference of a conductor then splits without a remainder
The first term is the Joule losses in the conductor, the second the share of the conductor in the losses in the earth and in the ground wires and the third the power delivered to the other conductors. The sum of the delivered powers over all conductors is zero. The table below the π-section tables gives the transfer between all pairs and the balance of each phase. A phase whose power difference is smaller than its Joule losses receives power from the others.
The transfer between pairs is usually larger than the differences \(\Delta P_i\). Power circulates between the phases even on a perfectly transposed line, in the direction L1, L2, L3, L1 when the inductive coupling prevails. Each phase then delivers as much as it receives. On an untransposed line the transfers around the loop are not equal and a difference is left to the phase.
The share \(\Delta P_{z,i}\) can also be negative. The earth is a common return path of all conductors and power is transferred between the phases through its resistance as well. Depending on how the phase current is rotated against the current returning through the earth, the phase delivers power to the earth or receives it from the earth. The sum over all phases is the losses in the earth and in the ground wires.
The arrows in the cross-section therefore show the net balance by default. A phase whose \(\Delta P_i\) is larger than its Joule losses has a surplus, a phase with a smaller \(\Delta P_i\) a deficit. In the chart the surplus is a solid grey area and the deficit a dashed area. The grey arrows split the surpluses between the phases of the same circuit in proportion to their deficits. The purple arrow between the centres of the circuits is the power that one circuit delivers to the other, that is the sum of the column to the other circuit in the table. The brown arrow at the earth is the share of the circuit in the losses in the earth and in the ground wires. The sums at the phases and circuits are exact, the assignment of pairs within a circuit is a convention.
The second arrow option draws the actual transfer through the coupling of each pair of conductors of a circuit including the circulating part. Between the circuits there are then two purple arrows, the sum of the transfers of all pairs in one and in the other direction. Their difference is the net transfer arrow. Through the coupling the circuits usually exchange several times more power than what finally remains with one of them.
Power difference of a phase and Joule losses
The difference \(\Delta P_k\) of one phase does not equal the Joule losses in the conductor of that phase. With balanced currents \(I\) and balanced phase voltages \(U_f\) it holds approximately for the phase L1 of one circuit
\(R_{ij}\) and \(X_{ij}\) are the real and imaginary parts of the elements of the matrix \(\mathbf{Z}\), \(B_{ij}\) the elements of the matrix \(\mathbf{B}\). The terms with the difference of reactances and with the difference of susceptances are active power transferred between the phases through the mutual inductances and mutual capacitances. They arise only when the couplings between the phases are not equal, that is on an untransposed line. Summed over the three phases they cancel. The first grows with the square of the current, the second depends on the voltage and acts even on an unloaded line. With a usual arrangement they have opposite signs and largely cancel around the surge impedance loading.
One phase therefore shows a larger power difference than the Joule losses in its conductor, and another a smaller or even a negative one. A negative difference \(\Delta P_k\) does not mean that the line generates energy, the total losses \(\Delta P\) are always positive. On a transposed line the differences \(\Delta P_k\) of all phases are equal. In the chart the solid coloured bar is the phase balance \(\Delta P_k\) and the hatched bar the Joule losses in its conductor, the dashed line is one third of the power difference of the circuit. The difference of the two bars is the power that the phase delivered to the other phases and to the earth and ground wires, or received from them. The delivered power is the solid grey area above the Joule losses, the received power the dashed area that takes away from the Joule losses. The grey number below the phase gives the same, positive for delivered and negative for received power.
Unbalance factors
The factor \(k_{Z2}\) tells how large a negative sequence voltage arises on the line with a purely positive sequence current, related to the positive sequence voltage drop. The factor \(k_{Z0}\) gives the same for the zero sequence. The factors \(k_{Y2}\) and \(k_{Y0}\) express the negative and zero sequence charging currents with a purely positive sequence voltage. With two circuits they are calculated from the self block of one circuit.
Per-unit values and matrix colouring
In per-unit values the phase matrices are related to the element \(Z_{L1L1}\) or \(Y_{L1L1}\), the sequence matrices to the positive sequence elements \(Z_{11}\) and \(Y_{11}\). In the phase matrix each element is compared with a transposed line, that is with the mean of the diagonal or off-diagonal elements of its block. In the coupling between the circuits it is compared with the mean of the whole block. The deviation related to the mean diagonal element sets the saturation of the red colour, full red corresponds to 10 % and more. In the sequence matrix the elements that are zero on a transposed line are coloured by the ratio \(|X_{ij}|/|X_{11}|\). The matrix frame is coloured by the largest deviation.
Effect of conductor height
With increasing height the self and mutual elements of the phase matrix \(\mathbf{Z}\) grow by the same value, so the positive sequence impedance \(Z_{1}\) does not change and the positive sequence capacitance \(C_{1}\) changes only slightly. Positive sequence currents return through the other phases and do not need the earth. The zero sequence returns through the earth, so \(Z_{0}\) grows and \(C_{0}\) decreases with the logarithm of the height.
Using the model
- The switch above the cross-section selects one or two circuits. With two circuits only the conductors of the right circuit and the ground wires to the right of the axis are moved, the left side mirrors itself.
- The phase conductor switch selects a triple bundle or a single conductor per phase.
- The phase order selection of the left circuit offers the basic mirror order, two rotations and three swaps of two phases. These are all the ways to assign three phases to three conductors.
- With snapping on the position is rounded to a 1 × 1 m grid, otherwise to 0.1 m. The coordinates can also be entered directly in the table. At most two ground wires can be added, with two circuits each wire off the axis is doubled.
- The sliders P and Q change the load of each circuit and the slider l the line length. The source voltage US is entered as a number, the default is 413 kV.
- The slider δ rotates the source phasors of the left circuit against the right one, a positive angle means leading.
- The arrows in the cross-section go from the phase that delivers power to the phase that receives it, the number is the power in MW. Net transfer draws arrows between the phases of a circuit and one purple arrow between the centres of the circuits. All pairs draws the transfer through the coupling of each pair of conductors of a circuit and between the circuits two arrows, the sum of the transfers in each direction. The third option turns the arrows off.
- In the chart the solid colour is the phase balance ΔP and the hatched bar the Joule losses. The solid grey area is the power that the phase delivers, the dashed area the power that it receives. The grey number below the phase is the same with a sign.
- The per-phase tables are below the cross-section, the left circuit on the left and the right one on the right. The summary of losses per circuit and in total is below the chart.
- The vertical axis of the chart is set from the load, the voltage and the line length and does not change with the arrangement as long as the values fit into the chart.
- The height slider with a logarithmic scale moves the whole arrangement from 1 m to 100 km.
- In the DISPLAY section you select the matrix form, the units, susceptance or capacitance and the Kron reduction of the ground wires.
- The results are rounded to three decimal places. Hovering over a matrix element shows its label and deviation, hovering over a voltage or current in the table also its angle.