Line model – PI sections (positive sequence)
Const. Z: Z = U_nom² / conj(S₃φ)
How the model works and what you can observe
The model shows the profile of the line-to-line voltage and the current along a line modelled as a series of PI sections, each 0.5 km long. The total line parameters (\(Z_1\), \(Y_1\)) are entered by the user. The voltage is given at the sending end (source), and the voltage and current at the receiving end are calculated. The load can be modelled in two ways, as a constant impedance or as a load with constant P and Q solved iteratively.
Load model – constant impedance (Z)
The load impedance is calculated from the nominal voltage \(U_{\text{nom}}\) and the specified three-phase power and does not change during the calculation:
The actual power drawn at the end of the line depends on the actual receiving-end voltage \(U_R\), not on the nominal \(U_{\text{nom}}\). Therefore, when \(U_R \neq U_{\text{nom}}\), the actual P and Q differ from the specified values:
Load model – constant P,Q (iterative method)
In this model the load always draws exactly the specified P and Q regardless of the actual voltage at the end of the line.
Since the load impedance depends on the receiving-end voltage and that voltage in turn depends on the load impedance, this is an implicit problem that is solved iteratively:
where \(U_R^{(k)}\) is the phase voltage at the end of the line in the \(k\)-th iteration. The algorithm converges when the relative change of \(|U_R|\) between iterations falls below \(10^{-9}\) (maximum 50 iterations).
Physical consequence: With constant P,Q the load model corresponds to a real load (e.g. an industrial one). A higher voltage leads to a lower current drawn (and vice versa), so the power drawn remains constant.
Transmission angle
The transmission angle \(\vartheta\) is the angle between the voltage phasors at the beginning and the end of the line, or between the voltage phasors of the busbars connected by the line. The transmission angle is important for the steady-state stability of the power system. The smaller the transmission angle, the larger the steady-state stability margin.
Losses
Active power losses are defined as the difference between the active power delivered to the system and the active power drawn from it. The only objective way of determining the losses in a system is to derive them from the delivered and drawn amounts of electrical energy measured by metering instruments:
Ferranti effect
The Ferranti effect occurs on electrical lines (especially MV cable lines and HV and EHV transmission lines) at light load or at no load. The voltage at the end of the line is then higher than the voltage at the beginning of the line.
The effect is caused by an excess of capacitive power on the line:
The Ferranti effect can raise the voltage in the electrical network above the permitted values. In practice it is handled by compensation, i.e. by connecting shunt reactors to the system.
Surge impedance loading (SIL)
The surge impedance loading \(\overline{S}_p\) is the power at which the voltage at the end of the line is almost the same as at the beginning (a voltage drop arises only on the line resistance). The line then behaves in the network as a purely resistive element and the balance of reactive powers is zero (exactly so for a lossless line):
The surge impedance loading for the nominal voltage \(U_n\) is given by:
where \(\overline{Z}_c = \sqrt{\overline{Z}_1 / \overline{Y}_1} = Z_c\angle\varphi_c\) is the surge impedance (characteristic impedance) of the line. For a lossless line \(\varphi_c = 0\) and the surge impedance loading is purely active. For a real line with resistance \(\varphi_c\) is a small negative angle, so the surge impedance loading also has a small negative reactive component \(Q_{\text{SIL}}\). A load with impedance \(\overline{Z}_c\) is therefore slightly capacitive.
The surge impedance loading is the limit at which the behaviour of the line changes:
- If the transmitted power is lower than \(P_{\text{SIL}}\), the line behaves as a capacitance: \[Q_C > \Delta Q_{\text{series}}\]
- If the transmitted power is higher than \(P_{\text{SIL}}\), the line behaves as an inductance: \[\Delta Q_{\text{series}} > Q_C\]
The surge impedance loading is not the limit of the maximum line loading. The maximum loading is given by the permissible current of the line, and SIL is also not a target value of the power transmitted on the line.
Propagation constant \(\gamma\) and surge impedance \(Z_c\)
For a line with per-unit-length parameters \(Z_1 = R_1 + jX_1\) [Ω/km] and \(Y_1 = G_1 + jB_1\) [S/km]:
The real part of \(\gamma\) (attenuation constant \(\alpha\)) corresponds to the attenuation of the wave along the line, the imaginary part (phase constant \(\beta\)) to the phase shift of the wave. For a lossless line (\(R_1 = 0, G_1 = 0\)) \(Z_c\) is real and the voltage profile at load \(P = P_{\text{SIL}},\; Q = 0\) is perfectly flat. For a real line with resistance, \(\overline{Z}_c\) is complex (small negative angle \(\varphi_c\)). At surge impedance loading \(\overline{S}_p = P_{\text{SIL}} + jQ_{\text{SIL}}\) the voltage decreases slightly along the line, approximately as \(e^{-\alpha x}\).
Matlab Simulink model 2019b
In the following file you will find a validation model built in MATLAB Simulink 2019.