Assessment of steady-state and transient stability of a synchronous generator
Moving a slider = immediate recalculation
Time waveforms – solution of the swing equation
Step-by-step method, Δt = 0.1 ms, without damping (no mechanical or electrical losses), constant e′ (no excitation control). CCT is determined as the limiting clearing time. When the fault is cleared at CCT, the load angle after the transition to curve III just reaches δ₁ and the generator swings without loss of synchronism, clearing 0.1 ms later already leads to loss of synchronism.
Calculation program for the assessment of steady-state and transient stability of a synchronous generator
The program calculates the quantities needed to assess steady-state stability and to analyse the transient stability of a synchronous generator connected to an infinite bus. It solves the operating states in normal operation and during a three-phase fault on one of the parallel lines or at the busbar.
Steady-state stability is assessed from the position of the generator operating point on its power-angle (internal) characteristic. The load angle and the steady-state stability margin are evaluated, the margin being given by the distance of the operating point from the maximum transmitted power.
Transient stability is analysed using the equal area criterion. The program calculates the accelerating and decelerating areas, the critical load angle and the critical fault duration, from which it determines whether the generator remains in synchronism with the network after the fault is cleared.
The calculations are made in the per-unit system. Active resistances and shunt admittances of lines and transformers are neglected.
Input parameters in per-unit values
Base values: \(U_{vz} = U_{nTS}\), \(S_{vz} = S_{nG}\), \(Z_{vz} = U_{vz}^{2}/S_{vz}\). Per-unit reactances of the generator, transformer and line:
Per-unit voltage, power and current:
Steady-state stability
The assessment of steady-state stability is based on the position of the generator operating point on its internal (power-angle) characteristic. The natural stability limit is 90°.
Transfer reactance and internal EMF (phasor, angle \(\vartheta_0\)):
Maximum power of the internal characteristic, delivered power and steady-state stability margin:
The basic assessment criteria are the load angle and the steady-state stability margin. The margin is expressed by the distance of the operating point from the point of maximum power on the internal characteristic of the generator, in terms of power or angle. As the load angle increases, the steady-state stability margin decreases, and after reaching the critical state corresponding to the maximum of the characteristic, the generator loses the ability to remain in synchronism with the network. Condition of steady-state stability:
Generator voltage, current and power (at the terminals):
Transient stability – three states of the system
I. State before the fault. Transfer reactance and transient internal EMF:
Excitation control of the generator is not considered, i.e. no change of the field current before the fault, during it or after it is cleared. The calculation therefore assumes a constant internal EMF of the generator behind the transient reactance.
II. State – three-phase fault. For a fault on one of the parallel lines at distance \(l_{skrat}\) (ratio \(m = l_{skrat}/l\)) the delta of impedances on the line is transformed into a star and the circuit is solved as a T-section:
For a busbar fault (\(l_{skrat} = 0\)):
III. State after the fault. For a fault on a line, the fault is cleared by tripping the faulted line:
For a busbar fault the theoretical assumption of complete fault removal is used, i.e. after the fault is cleared the system returns to the original state and both parallel lines remain in operation (\(x_{III} = x_{I}\), \(p_{mIII} = p_{mI}\)).
A busbar fault causes the largest drop of the transmitted generator power during the fault and therefore the largest acceleration of the rotor. For this reason the calculated critical angle and critical fault duration give a conservative assessment of the transient stability of the generator.
Equal area criterion – qualitative assessment of transient stability
The equal area criterion is based on the kinetic energy balance of the generator rotor during the fault and after it is cleared. During the fault the transmitted electrical power drops, so the mechanical power of the turbine exceeds the electrical power of the generator. The rotor therefore accelerates and its kinetic energy increases, which is represented graphically by the accelerating area \(S^{+}\). After the fault is cleared the electrical power of the generator increases and can exceed the mechanical power supplied by the turbine. The rotor then decelerates, which is represented by the decelerating area \(S^{-}\).
The generator remains transiently stable if the decelerating area is at least equal to the accelerating area. The critical angle \(\delta_{krit}\) is determined from the condition of equal accelerating and decelerating areas \(S^{+} = S^{-}\):
The angles in the equation for \(\delta_{krit}\) and in the expressions for the areas are in radians.
Accelerating and decelerating area for the clearing angle \(\delta_{vyp}\):
If the fault is cleared at an angle smaller than \(\delta_{krit}\), \(S^{-} \ge S^{+}\) holds and the generator remains transiently stable. Conversely, if the fault is cleared at an angle larger than \(\delta_{krit}\), the generator loses synchronism with the network.
If \(p_{mII} > p_{0}\), it must first be checked whether a critical angle exists at all. In this case a decelerating region can also appear during the fault, so the accelerating area \(S^{+}_{skrat} = \int_{\delta_0}^{\delta_2}\left(p_0 - p_{mII}\sin\delta\right)d\delta\) (where \(\delta_2 = \arcsin(p_0/p_{mII})\)) is compared with the decelerating area \(S^{-}_{skrat} = \int_{\delta_2}^{\delta_3}\left(p_{mII}\sin\delta - p_0\right)d\delta\) (where \(\delta_3 = \pi - \delta_2\)), which already arises during the fault. A critical angle exists only if the accelerating area is larger than the decelerating area arising during the fault. Otherwise the generator does not lose synchronism even if the fault is not cleared.
Critical clearing time – quantitative assessment of transient stability
The critical clearing time (CCT) is the maximum permissible time the fault can last without loss of synchronism of the generator. It corresponds to the instant when the rotor load angle reaches the critical value \(\delta_{krit}\). The critical time is determined from the time course of the rotor load angle, which is given by the solution of the swing equation of the synchronous generator:
The swing equation is solved numerically by the step-by-step method, in which time is divided into small intervals \(\Delta t\). In each interval the rotor motion is approximated assuming constant values of the quantities involved:
Solving the swing equation step by step gives the time course of the load angle \(\delta(t)\). The critical fault duration is the time at which the load angle first reaches the critical angle \(\delta_{krit}\).
After clearing a fault on one of the lines, the angle does not oscillate around \(\delta_{0}\) but around the equilibrium angle \(\delta_{0}' = \arcsin(p_{0}/p_{mIII})\), the intersection of \(p_{0}\) with the post-fault curve (the curve \(p_{mI}\) no longer exists after the line is tripped). For a busbar fault \(\delta_{0}' = \delta_{0}\), in practice the differences are almost invisible. The swing period is determined from \(\delta(t)\) as the time of the first upward return to \(\delta_{0}'\).