Interactive visualization of higher harmonics
Higher harmonics are sinusoidal voltage or current waveforms whose frequency is an integer multiple of the fundamental frequency. Higher harmonics are among the basic indicators of power quality. The permitted harmonic levels in electrical networks are defined in EN 50160 and in the Technical Conditions of the transmission and distribution system operators.
Undesirable effects of higher harmonics include:
- an increase in the total current, which can cause overheating of equipment and higher losses:
\[I_\mathrm{RMS} = \sqrt{I_1^2 + I_2^2 + I_3^2 + I_4^2 + I_5^2 + \dots + I_n^2}\]where \(I_{2H}\) to \(I_{nH}\) are the magnitudes of the 2nd to n-th current harmonics and \(I_{1H}\) is the fundamental,
- a stronger skin effect, which can cause overheating of conductors and higher losses,
- mechanical vibrations and higher losses in rotating machines,
- overloading of the neutral conductor in a three-phase network,
- undesirable resonance phenomena in the electrical network,
- higher frequency-dependent losses (e.g. hysteresis losses, eddy current losses).
The 3rd, 5th and 7th harmonics occur most often in electrical networks. Each harmonic is defined not only by its magnitude but also by its phase shift.
THD (Total Harmonic Distortion)
THD (Total Harmonic Distortion) is a quantity that expresses the degree of distortion (deviation from the sinusoidal waveform) of a voltage or current caused by higher harmonics. The permitted THD values in electrical networks are defined in EN 50160 “Voltage characteristics of electricity supplied by public electricity networks” and in the Technical Conditions of the transmission and distribution system operators. The higher the THD, the more distorted the voltage or current waveform.
Mathematical definition:
where
\(U_{2H}\) to \(U_{nH}\) – magnitudes of the 2nd to n-th voltage (or current) harmonic,
\(U_{1H}\) – fundamental harmonic.
Higher harmonics and sequence systems
1st harmonic (fundamental)
Behaves as a positive sequence system, phase sequence L1, L2, L3, phase shift 120°:
3rd harmonic and its multiples (triplen harmonics)
Behaves as a zero sequence system, phases L1, L2, L3 are in phase, phase shift 0°:
As a consequence of triplen harmonics the neutral conductor is overloaded, because it carries a 3rd harmonic current three times larger than the phase conductor:
5th harmonic
Behaves as a negative sequence system, phase sequence L1, L3, L2, phase shift 120°. It creates a rotating magnetic field in the direction opposite to the fundamental, which leads to increased noise and losses in rotating electrical machines: