Mechanics of a suspended conductor – catenary in a span

Mechanics of a suspended conductor – catenary in a single span

CALCULATION RESULTS
—
SPAN GEOMETRY
W = V₂ − V₁ = 0.0 m
CONDUCTOR TENSION
Three views of the same quantity: Fh = σh·S, c = Fh/(wc·g). Conductor without additional load (z = 1). The effect of ice and temperature is handled by the state change equation mode.
SAG DISPLAY
CONDUCTOR 382-AL3/49-ST1A
wc= 1.4523 kg/m
d= 27 mm
S= 431.2 mm²
α= 1,94·10⁻⁵ 1/°C
E= 67 100 MPa
RTS= 121 300 N

Catenary equation and its shift to span coordinates

A conductor fixed at two suspension points takes the shape of a catenary under its own weight. The solution of the differential equation of the sagging conductor is the function \(y = c\cdot\cosh(x/c)\), where \(c\) is the catenary parameter. It is given by the ratio of the horizontal force to the conductor weight per unit length, and the additional load (ice, wind) enters through the overload factor \(z\):

\[ \sigma_h = \frac{F_h}{S},\qquad c = \frac{F_h}{w_c\,g\,z} = \frac{\sigma_h\,S}{w_c\,g\,z} = \frac{\sigma_h}{\gamma\,z}, \qquad \gamma = \frac{w_c\,g}{S} \]

To calculate the conductor position relative to the terrain, it is convenient to shift the coordinate system so that the origin lies at the foot of the first tower. The catenary is shifted by \(a'\) in the \(x\) direction and by \(-c+h\) in the \(y\) direction:

\[ g(x) = c\cdot\cosh\left(\frac{x-a'}{c}\right) - c + h \]

The quantity \(a'\) is the horizontal distance from the first tower to the lowest point of the conductor and \(h\) is the height of this point above zero. From the height difference of the suspension points \(W = V_2 - V_1\) it follows that:

\[ a' = a - \left[\mathrm{asinh}\left(\frac{V_2-V_1}{2c\,\sinh\frac{a}{2c}}\right) + \frac{a}{2c}\right]\cdot c \qquad h = V_1 - c\cdot\cosh\left(\frac{a'}{c}\right) + c \]

The conductor length in an inclined span is obtained by a curve integral from \(0\) to \(a\):

\[ l = c\left[\sinh\left(\frac{a-a'}{c}\right) + \sinh\left(\frac{a'}{c}\right)\right] \]

In a level span the length can be approximated by the first two terms of the Taylor series:

\[ l \approx a + \frac{a^3}{24c^2} \]

Sags

The sag is the vertical distance between the chord connecting the suspension points and the conductor. The chord is the line \(k(x) = \frac{V_2-V_1}{a}x + V_1\) and the sag at any point is \(f_x = k(x) - g(x)\). Three characteristic values are distinguished.

The maximum sag refers to an ideal (level) span. It is measured from the horizontal line \(j = \max(V_1, V_2)\) to the lowest point of the conductor, i.e. at \(x = a'\):

\[ f_{max} = j - g(a') = j - h \]

The characteristic sag is the vertical distance between the chord and the conductor at mid-span:

\[ f_{cha} = k\left(\frac{a}{2}\right) - g\left(\frac{a}{2}\right) \]

The visible sag is the actual largest sag in an inclined span. It is located where the tangent to the sag curve is parallel to the chord, i.e. where the first derivative equals \(\tan\Phi = \frac{V_2-V_1}{a}\):

\[ x_{vid} = \mathrm{asinh}\left(\frac{V_2-V_1}{a}\right)\cdot c + a' \qquad f_{vid} = k(x_{vid}) - g(x_{vid}) \]

Note on the tension modes. With direct input, \(\sigma_h\) and \(z\) are set independently. This is useful for exploring the shape of the catenary for a chosen tension and load. It does not, however, model the response of the span. If ice settles on the conductor, the span is fixed and the conductor can only elongate elastically, so both the sag and the tension increase. This is what the second mode, the state change equation, is for.

State change equation

The state change equation converts the mechanical stress from a known state \(0\) (\(\sigma_{h0}\), \(\vartheta_0\), \(z_0\)) to a new climatic state \(1\) given by the temperature \(\vartheta_1\) and the overload \(z_1\):

\[ \sigma_{h1}^{3} + \sigma_{h1}^{2}\left[\frac{\gamma^2 E}{24} \left(\frac{a_{St}\,z_0}{\sigma_{h0}}\right)^{2} + \alpha E(\vartheta_1-\vartheta_0) - \sigma_{h0}\right] = \frac{\gamma^2 E}{24}\,(a_{St}\,z_1)^{2} \]

It is a cubic equation with \(A = 1\) and \(C = 0\), whose real root can be expressed analytically. The span \(a\) is replaced in it by the ruling span \(a_{St}\). For a single span with height difference \(\Delta h\) it gives:

\[ a_{St} = \frac{a^{2}}{\sqrt{a^{2}+\Delta h^{2}}} \]

The calculated \(\sigma_{h1}\) then determines \(F_h = \sigma_{h1} S\) and the parameter \(c = \sigma_{h1}/(\gamma z_1)\), and thus the whole shape of the sag curve. Heating of the conductor reduces the stress and increases the sag, while additional ice load increases the stress. In Slovak conditions the temperature \(-5\,^\circ\mathrm{C}\) is normally chosen as state \(0\).

In a level span (\(V_1 = V_2\)) all three sags coincide in one value at mid-span, because \(a' = a/2\) and \(x_{vid} = a/2\).

In an inclined span only \(f_{max}\) differs noticeably, because it is measured from the horizontal line \(j\). The characteristic and visible sags remain almost identical, and this is not a calculation error. The location of the largest sag is only this far from mid-span:

\[ x_{vid} - \frac{a}{2} = \frac{a^{2}}{24c}\cdot\frac{u}{\sqrt{1+u^{2}}}, \qquad u = \frac{V_2-V_1}{a} \]

Since the sag curve has zero derivative around its maximum, it is very flat there and the difference in values is only of second order:

\[ f_{vid} - f_{cha} \approx \frac{\left(x_{vid}-\frac{a}{2}\right)^{2}}{2c} \]

For common spans this amounts to hundredths to tenths of a millimetre (e.g. \(a = 300\) m, \(W = 15\) m, \(\sigma_h = 30\) MPa → \(x_{vid}\) is 0.21 m from mid-span and the difference in sags is only 0.023 mm). This is why the characteristic sag at mid-span is used in practice, it is easy to measure and differs negligibly from the actual maximum. The difference grows only at very low tension and a large height difference, for \(a = 500\) m, \(W = 200\) m and \(\sigma_h = 6\) MPa it is already about 0.9 m. The results panel lists the difference \(f_{vid} - f_{cha}\) in millimetres, so this can be checked.