Electric power
Electric power is a physical quantity that expresses the amount of electrical energy transferred or consumed per unit of time. If the voltage \(u(t)\) and the current \(i(t)\) vary sinusoidally, their instantaneous values are given by:
The instantaneous power is then:
In terms of RMS values:
This expression can be rearranged further using the well-known identity1:
It follows that the instantaneous AC power is a function of time and oscillates at twice the frequency around the value \(U_{\text{RMS}} I_{\text{RMS}} \cos \varphi\), as shown in the figure.
When \(-90^\circ < \varphi < 90^\circ\), the power curve becomes negative twice in every period and the duration of each negative interval is:
During these intervals the power is negative, which means that energy flows in the opposite direction, from the load back to the source.
For \(\varphi = 0\), that is, when the current and voltage are in phase, we get:
In this case the whole power curve \(p(t)\) lies in the positive region and the power is at its maximum.
Conversely, if \(\varphi = 180^\circ\), the current is in antiphase with the voltage, so \(p(t)\) is negative over the whole period and the power flows in the opposite direction, from the load to the source.
If \(\varphi = 90^\circ\) or \(\varphi = -90^\circ\), that is, when the current and voltage are shifted by a quarter of a period, then:
In this case the power curve is a sinusoid at twice the frequency, symmetrical about the axis, with equal positive and negative areas. The resulting power over one period is therefore zero.
In general, the active power \(P\) over one period is determined as:
The second term \(\int_{0}^{T} \cos(2\omega t - \varphi) \, dt\) is zero, because the mean value of \(\cos(2\omega t - \varphi)\) over one period is zero.
The final expression for the active power of alternating current is therefore:
The product of the RMS voltage and current alone does not give the power. The real power is obtained only by multiplying this product by the cosine of the phase shift \(\varphi\) between current and voltage. This factor is called the power factor. The product of the RMS values itself is called the apparent power \(S\) [VA]:
On this basis the apparent power can be split into its real component, the active power \(P\), and its imaginary component, the reactive power \(Q\) [VAr]:
The relation between \(P\), \(Q\) and \(S\) is shown in the power triangle. The apparent power can be determined from \(P\) and \(Q\) as:
and the power factor as:
If the phase shift \(\varphi\) is non-zero, reactive power appears and the apparent power is greater than the active power. If this angle lies in the interval \(\langle -90^\circ, 90^\circ \rangle\), the active power still flows from the source to the load. For \(\varphi < 0\) the power is said to be capacitive, and for \(\varphi > 0\) inductive. The phase shift between current and voltage is caused by capacitive or inductive reactance, which makes the current lag the voltage (inductor) or the voltage lag the current (capacitor).
1 \(\sin \alpha \cdot \sin \beta = \tfrac{1}{2} [ \cos(\alpha - \beta) - \cos(\alpha + \beta) ]\)